FM4882 is a new standard of interior
wall materials for clean room, developed by FM Global and the current FM4880 standard,"Class
1 Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels,
Interior Finish Materials or Coatings, and Wall Systems." Additionally, Class1 is required on ASTM E84 standard which is "Standard Test Method for Surface Burning Characteristics of Building Materials"
FM 4882 is applied to products used as interior wall materials
for clean rooms in the pharmaceutical and food processing plants,
and this standard intends to minimize the possible safety hazards
and risks, in the event of an unexpected fire (to suppress the
spread of fire and minimize possible damage due to smoke generation). |
FM4882
standard =
FM4880 standard + ASTM E84 standard + 16ft High parallel panel test
|
|
FM4880
standard
Evaluation items
- Room Fire
Test
Qualifies Panels for Use Up to 10 ft in Height
- 25 ft Corner Test (Optional )
Qualifies Panels for Use Up to 30 ft in Height
- 50 ft Corner Test (Optional)
Qualifies Panels for Use to Unlimited Heights
ASTM E84 standard
ASTM E84 standard is for surface burning characteristics of Building materials.
Evaluation items
- SDI(Smoke Developed Index)
- FSI(Flame Spread Index)
Criteria for conformance to the standard
Class T/A SDI:0-25, FSI≤450
Class U/B SDI:26-75, FSI≤450
Class V/C SDI:76-200, FSI≤450
16ft High Parallel Panel Test
FM Approvals 4.9m(16ft) High Parallel Panel Test.
•Average Smoke emission rate(Gsmoke)
|
|
Those products that pass the tests specified in both
standards are listed as FM4882 approved products. |
| * TAKIRON "IVY-ONE" is
an FM4882 standard approved product for applications involving
heights of up to 30 ft. |
Takiron "IVY-ONE" (IVY573) |
 Non FM Plastics Sheet
(Polypropylene) |
|