What is FM4882?
FM4882 is a new standard of interior wall materials for clean room, developed by FM Global and the current FM4880 standard,"Class 1 Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coatings, and Wall Systems." Additionally, Class1 is required on ASTM E84 standard which is "Standard Test Method for Surface Burning Characteristics of Building Materials"
FM 4882 is applied to products used as interior wall materials for clean rooms in the pharmaceutical and food processing plants, and this standard intends to minimize the possible safety hazards and risks, in the event of an unexpected fire (to suppress the spread of fire and minimize possible damage due to smoke generation).
FM4882 standard =
FM4880 standard + ASTM E84 standard + 16ft High parallel panel test
FM4880 standard
Evaluation items
  1. Room Fire Test
    Qualifies Panels for Use Up to 10 ft in Height

  2. 25 ft Corner Test (Optional )
    Qualifies Panels for Use Up to 30 ft in Height

  3. 50 ft Corner Test (Optional)
    Qualifies Panels for Use to Unlimited Heights

ASTM E84 standard
ASTM E84 standard is for surface burning characteristics of Building materials.

Evaluation items

  1. SDI(Smoke Developed Index)

  2. FSI(Flame Spread Index)


Criteria for conformance to the standard
Class T/A SDI:0-25, FSI≤450
Class U/B SDI:26-75, FSI≤450
Class V/C SDI:76-200, FSI≤450
16ft High Parallel Panel Test
FM Approvals 4.9m(16ft) High Parallel Panel Test.
•Average Smoke emission rate(Gsmoke)
  Those products that pass the tests specified in both standards are listed as FM4882 approved products.
* TAKIRON "IVY-ONE" is an FM4882 standard approved product for applications involving heights of up to 30 ft.
Takiron "IVY-ONE" (IVY573)
Non FM Plastics Sheet (Polypropylene)